Clean Water Production Capacity 1250 litre per hour,
Input water quality TDS < 40.000PPM ( recommended)
Output water quality TDS < 400 PPM,
Salt Rejection Rate 98% ,
Recovery Rate( pure water : inlet water) 50~ 75%
Input Power( standard) AC380V / 50Hz
Pre-treatment Filtration:
By Activated Sand 16" x 62" - 1 Unit
Big Blue PP Catridge Filter Pores Size 1 Micron
Main unit:
First stage Pump for Prefilter Pump SUS-316 1500W x 380V
High Pressure Pump ( AXIAL DUPLEX 2205 PUMP ) 7,5 KW x 380V
Membrane SW 8" x 40" 2 PC
Hi-Pressure Membrane housing 8” x 40” -2 Piece
Main frame steel coating
Accessories
Piping Low pressure: PVC quick connection ,
For Hi-pressure Using Hose, Electrical Parts
Flow metre, TDS metre, pressure metre, electromagnetic valve, etc.
and built-in RO membrane washing device, VSD Inverter
Total Weight : Approx. < 800 Kgs